GD Midea Refrigerant Equipment Co. Ltd                                 Service manual for Electrolux split Series 
24 
PROBLEM CAUSE  REMEDY 
Outdoor transformer 
failure 
Replace if failure. 
Indoor PCB failure  Replace the PCB if the photon coupling on indoor PCB is failure. 
Insufficient 
cooling or 
heating. 
Indoor PCB failure  Replace after checked failure. 
Lack of refrigerant   
Check leakage. Recycle the refrigerant. Correct and recharge if there is 
any leakage in the refrigerant system. 
Soft starter module 
failure 
Check the module and the capacitor connected to the module. Replace 
if failure. 
Overcurrent protector 
failure 
Check the resistance of compressor overcurrent protector. Replace if 
failure. 
Compressor 
protection 
Outdoor PCB failure  Replace after checked failure. 
Temperature sensor 
failure 
Replace after checked failure. 
Connector failure or 
loose 
Repair or replace the sensor. 
Open or short 
circuit of outdoor 
temperature 
sensor 
Outdoor PCB failure  Replace after checked failure. 
Temperature sensor 
failure 
Replace after checked failure. 
Connector failure or 
loose 
Repair or replace the sensor. 
Room temp or 
evap temp 
sensor open or 
short circuit 
Indoor PCB failure  Replace after checked failure. 
Soft starter module 
failure 
Check the module and the capacitor connected to the module. Replace 
if failure. 
Over load or too 
low voltage 
protection 
Power failure  Wait if checked the power voltage is really too low. 
Wiring failure  Correct if indoor fan motor wiring is loose. 
Indoor fan motor 
failure 
Check the input of fan motor. Replace if failure. 
Fan speed 
beyond control 
Indoor PCB failure  Replace after checked failure. 
Zero-crossing 
error 
Indoor PCB failure  Replace after checked failure. 
LED failure  Replace the display if checked failure. 
No display on 
indoor unit. 
Remote control shut 
the display 
Push the button to turn the display on. 
No power  Check the voltage. Call an electrician if not within the limit. 
Wiring  Check the terminals. Repair and correct if loose. 
Temperature setting  Check and adjust the temperature setting. 
Mode setting  Check and adjust the mode setting. 
Soft starter module 
failure 
Check the module and the capacitor connected to the module. Replace 
if failure. 
Reverse valve 
solenoid coil 
Check the reverse valve solenoid coil. Replace the coil if short, open or 
damaged.  
No cooling or 
heating. 
Reverse valve 
If the reverse valve is blocked, the heating mode will not perform. 
Replace the reverse valve after checking the reason.