GD Midea Refrigerant Equipment Co. Ltd                                 Service manual for Electrolux split Series 
13 
those of the indoor unit.) 
1. Lift the front panel up and remove the   
window cover from the indoor unit by   
loosening the screw. 
2. Connect wires to the Indoor Unit terminals   
from the Outdoor Unit as identified by their   
colors. 
3. Secure the cable with the cord clamp. 
4. Wrap wires (conductors) that were not   
connected with insulating tape so that they do   
not touch any electrical or metal parts. 
 
Notes:  
Wrong wire connection may cause some   
electrical parts to malfunction.   
The length of the power supply cord should   
be at least 1.8m measured from the power   
supply cord entry of the cabinet to the middle   
of the live pin of the plug. 
2.5.2 Connect the cable to the outdoor unit 
2.5.2.1 Remove the control cover from the unit by 
loosening the screw. Connect the wires to the 
terminals on the control board individually.   
2.5.2.2 Secure the cable onto the control board 
with the cord clamp. 
2.5.2.3 Re-fix the control cover to the original 
position with the screw. 
2.5.2.4 Use a recognized circuit breaker (Refer to 
table on page 11.) between the power source and   
the unit. An isolation device to adequately 
disconnect all supply lines must be fitted. 
 
 
CAUTIONS:
 
After confirming the above conditions, prepare the 
wiring as follows: 
1)  Never fail to have an individual power circuit   
specifically for the air conditioner. As for the   
method of wiring, be guided by the circuit   
diagram posted on the inside of control cover. 
2)  The screws which fasten the wiring in the 
  casing of electrical fittings may come loose   
  from vibrations to which the unit is subjected   
during the course of transportation. Check   
them and make sure that they are all tightly   
fastened. If they are loose, it could cause   
burn-out of the wires. 
3)    Specification of power source. 
4)    Confirm that electrical capacity of the   
installation is sufficient. 
5)    Ensure that the starting voltage is maintained   
at more than 90 percent of the rated voltage   
marked on the name plate. 
6)  Confirm that the cable thickness is as   
specified in the power source specification.   
Particularly note the relation between cable   
length and thickness. (Refer to page 11.) 
7)    Always install a Residual Current Device 
(RCD) in wet or moist area. 
8)    The following may be caused by voltage drop. 
        Vibration of a contactor, which will damage   
the contact point, fuse blowing, disturbance of   
the normal function of the overload. 
9)  The means for disconnection from a power   
supply shall be incorporated in the fixed   
wiring and have an air gap contact separation   
of at least 3mm in each active (phase)   
conductor. 
 
 
If a power plug is not to be used, provide a Circuit 
Breaker/Fuse between power source and the unit 
as shown in adjacent diagram.