Addresses below can be used as 03(Read Holding Registers), 06(Write
Single Register)
Data Content Address of
Register
Notes
FORCED HEAT2 ON 202+(Unit
Address) *100
Enable/Disable
1/0 (Available for multiple pump)
Set as 1 is invalid before HEAT2
ENABLE is set as YES.
DHW SWITCH 206+(Unit
Address) *100
Enable/Disable
1/0 (Available for multiple
pump
DHW MODE ON/
OFF
207+(Unit
Address) *100
Enable/Disable
Set as 1 is invalid before DHW
SWITCH is set as YES.
1/0 (Available for multiple
pump
Water Set
Temperature of the
selected unit
217+(Unit
Address) *100
(30°C~60°C)
(Available for multiple pump)
Note: 1. 06 Write register, if the value is written beyond the scope of the note,
the exception code is returned.
2. Unit Address stands for machine address 0-15, 0 stands for host 0.