M‐ThermalSplit
20190949
Procedure
E5/E6/E9/EA
Temperaturesensorconnectionon
outdoorunitmainPCBisloose
1
Yes
Ensurethesensorisconnectedproperly
No
Temperaturesensorhasshort‐circuited
orfailed
2
Yes
Replacethesensor
No
ReplaceoutdoorunitmainPCB
Notes:
1. AirsideheatexchangerrefrigerantoutlettemperaturesensorandoutdoorambienttemperaturesensorconnectionsareportCN9ontheoutdoorunit
mainPCB(labeled12inFigure4‐2.2inPart4,2.3"MainPCBsforRefrigerantSystem,InverterModule".Dischargepipetemperaturesensorconnectionis
portCN8ontherefrigerantsystemmainPCBs(labeled11inFigure4‐2.2inPart4,2.3"MainPCBsforRefrigerantSystem,InverterModule").Suctionpipe
temperaturesensorconnectionisportCN1onthemaincontrolboard(labeled13inFigure4‐2.2inPart4,2.3"MainPCBsforRefrigerantSystem,Inverter
Module").
2. Measuresensor resistance.If the resistanceis toolow, the sensorhasshort‐circuited.Iftheresistanceisnotconsistentwith thesensor’s resistance
characteristicstable,thesensorhasfailed.RefertoTable4‐5.1,andTable4‐5.2inPart4,5.1“TemperatureSensorResistanceCharacteristics”.