MideaM‐ThermalSplitServiceManual
4.6 EETroubleshooting
Digitaldisplayoutput
Description
HydronicboxmainPCBEEPROMerror.
M‐ThermalSplitstopsrunning.
ErrorcodeisdisplayedonhydronicboxmainPCBanduserinterface.
Possiblecauses
HydronicboxmainPCBEEPROMisnotconnectedproperly.
HydronicboxmainPCBdamaged.
Procedure
EE 


HydronicboxmainPCBEEPROM
1
isnot
connectedproperly
Yes
EnsuretheEEPROMisconnected
properly
No

ReplacehydronicboxmainPCB
Notes:
1. HydronicboxmainPCBEEPROMisdesignatedIC18onthemainPCBforhydronicbox(labeled32inFigure4‐2.1inPart4,2.2"MainPCBforHydronic
System").