EasyManua.ls Logo

Midea M3OF-27HFN8-Q - Troubleshooting

Midea M3OF-27HFN8-Q
69 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10. Troubleshooting
10.1 Indoor unit error code explanation:
For Aurora type ,All Easy type, Forest type,
Four-way cassette type (compact), A6 Duct:
Malfunction
Error Code
Timer Lamp
Operation Lamp
(flashes)
Indoor EEPROM malfunction E0 X 1
Communication malfunction between indoor and outdoor units E1 X 2
Indoor fan speed has been out of control E3 X 4
Open or short circuit of T1 temperature sensor E4 X 5
Open or short circuit of T2 temperature sensor E5 X 6
Refrigerant leakage detection EC X 7
Water level alarm
EE X 8
Overcurrent protection (For some units) F0 O 1
Open or short circuit of T4 temperature sensor F1 O 2
Open or short circuit of T3 temperature sensor F2 O 3
Open or short circuit of T5 temperature sensor F3 O 4
Outdoor EEPROM malfunction (For some units) F4 O
5
Outdoor fan speed is out of control F5 O
6
Open or short circuit of T2B temperature sensor F6 O
7
Communication malfunction between indoor two chips(For A6 Duct) FA O 11
IPM module malfunction P0
1
Over voltage or over low voltage protection P1
2
Too low ambient temperature protection P3
4
Inverter compressor drive protection P4
5
Indoor units mode conflict -- 6
Low pressure protection of compressor P6
7
O (on) X(off) (flash at 2Hz)

Other manuals for Midea M3OF-27HFN8-Q

Related product manuals