Electrical Control Function
Electrical Control System 117
T
ime2
Time conditions(Meet the following conditions)
1.Running in heating mode
2. T4<3
3. Compressor is on
4. T3TempEnterDefrost_ADD
Cleared conditions (Meet any one of the following conditions)
1. Compressor is off and T3TempEnterDefrost_ADD +2 last for 20 minutes
2. Running in cooling mode.
3. Compressor is off for 1 hour.
Condition of entry defrosting:
time1+ time240 minutes, When defrosting is end,time1 and time2 are cleared.
Condition of ending defrosting:
If any one of following items is satisfied, defrosting will stop and the machine will turn to normal heating
mode.
The defrosting time achieves 10min;
T3 15;
T3 7 for 60seconds.
Defrosting action
4-Way valve
Indoor fan
Outdoor fan
480P
PMV
PMV running
8 mins with 300P
Compressor
10S 30S
TimeA
10S
no longer than 10min