8.4.2.11 P4 (Temperature protection of compressor discharge) diagnosis and solution.
Error Code
P4
Malfunction conditions
When the compressor discharge temperature(T5) is more
than 115 for 10 seconds, the compressor will stop
and
restart till T5 is less than 90.
Potential causes
Refrigerant leakage
Wiring mistake
Faulty discharge temperature sensor
Faulty outdoor PCB
Trouble shooting: