EasyManuals Logo

Midea MHA-V6W/D2N8-B User Manual

Midea MHA-V6W/D2N8-B
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #104 background imageLoading...
Page #104 background image
M thermal Split
202004 103
4.24 C7 Troubleshooting
Digital display output 4.24.1
Description 4.24.2
Transducer module temperature too high protection
M thermal Split stops running.
Error code is displayed on hydronic box main PCB and user interface.
Possible causes 4.24.3
Power supply voltage of the unit is low.
The space between the units is too narrow for heat exchanger.
Heat exchanger is dirty or something is block on the surface.
Fan is not running.
Water flow rate is low.
Water outlet temp. sensor is loosen or broken.
Midea CAC
Confidential

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MHA-V6W/D2N8-B and is the answer not in the manual?

Midea MHA-V6W/D2N8-B Specifications

General IconGeneral
BrandMidea
ModelMHA-V6W/D2N8-B
CategoryAir Conditioner
LanguageEnglish

Related product manuals