EasyManuals Logo

Midea MHA-V6W/D2N8-B User Manual

Midea MHA-V6W/D2N8-B
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #69 background imageLoading...
Page #69 background image
M thermal Split
68 202004
Midea M thermal Split
Service Manual
4.12 H6, HH Troubleshooting
Digital display output 4.12.1
Description 4.12.2
H6 indicates a DC fan error.
HH indicates that H6 protection has occurred 10 times in 2 hours. When HH error occurs, a manual system restart is
required before the system can resume operation. The cause of HH error should be addressed promptly in order to
avoid system damage.
M thermal Split stops running.
Error code is displayed on outdoor unit main PCB and user interface.
Possible causes 4.12.3
DC fan wire is loosed.
High wind speed.
Fan motor blocked or has failed.
Invert module damaged.
Main PCB is damaged.
Midea CAC
Confidential

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MHA-V6W/D2N8-B and is the answer not in the manual?

Midea MHA-V6W/D2N8-B Specifications

General IconGeneral
BrandMidea
ModelMHA-V6W/D2N8-B
CategoryAir Conditioner
LanguageEnglish

Related product manuals