EasyManuals Logo

Midea MHA-V6W/D2N8-B User Manual

Midea MHA-V6W/D2N8-B
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #73 background imageLoading...
Page #73 background image
M thermal Split
72 202004
Midea M thermal Split
Service Manual
4.15 P0, HP Troubleshooting
Digital display output 4.15.1
Description 4.15.2
P0 indicates suction pipe low pressure protection. When the suction pressure falls below 0.14MPa, the system
displays P0 protection and M thermal Split stops running. When the pressure rises above 0.3MPa, P0 is removed and
normal operation resumes.
HP indicates Pe<0.6Mpa occurred 3 times in an hour.
Error code is displayed on outdoor unit main PCB and user interface.
Possible causes 4.15.3
Low pressure switch not connected properly or has malfunctioned.
Insufficient refrigerant.
Low pressure side blockage.
Poor evaporator heat exchange in heating mode or DHW mode.
Insufficient water flow in cooling mode.
Outdoor unit main PCB damaged.
Midea CAC
Confidential

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MHA-V6W/D2N8-B and is the answer not in the manual?

Midea MHA-V6W/D2N8-B Specifications

General IconGeneral
BrandMidea
ModelMHA-V6W/D2N8-B
CategoryAir Conditioner
LanguageEnglish

Related product manuals