L4 troubleshooting(the same as L1/L2) 4.21.8
Situation 1: L4 error appears immediately after the outdoor unit is powered-on
L4
Replace the inverter PCB
Condition 2: L4 error appears after the compressor has been running for a period of time and the compressor speed is
over 60rps
L4
Compressor is over-current
2
Yes
Replace the compressor
No
Replace the inverter PCB
Notes:
1. Re-start the unit, use clip-on ammeter to measure the compressor current, if the current is normal indicates the compressor is failed, if the current is
abnormal indicates the inverter PCB is failed..
L5/L8/L9 troubleshooting 4.21.9
L5/L8/L9
The wire is not connected properly
NO
Ensure wire is connected properly
Yes
Inverter module PCB has malfunctioned
Yes
Replace inverter module PCB
No
Replace the compressor