Electrical Control Function 
Electrical Control  233 
T3
Above and below
outdoor fan  on
Above outdoor fan on
 
 
1.3.2.3 Indoor Fan Running Guidelines 
In cooling mode, the indoor fan runs continuously. 
You can select the following speeds: high, 
(medium), low, or auto. 
The  auto  fan  acts  according  to  the  following 
principles: 
For floor standing units: 
High
Low
 
For other units: 
T1-Ts
High
Low
Medium
 
1.3.2.4  Low  evaporator  coil  temperature  T2 
protection 
T2
On
Off
 
When  the  evaporator  temperature  goes  below  a 
preset value, the compressor stops. 
 
1.3.2.5  Condenser  high  temperature  T3 
protection(excluding  12~36k  cooling  only 
models) 
T3
Off
On
 
When  condenser  temperature  exceeds  the  preset 
value, the compressor stops. 
 
1.3.3 Heating Mode(For heat pump models) 
1.3.3.1 Compressor Running Guidelines 
Once the compressor starts up, it keeps running 7 
minutes, then it will follow the below rules: 
When  T1-Ts  is  higher  than  setting    value,  the 
compressor  and  outdoor  fan  will  shut  off.  When 
T1-Ts is lower than setting    value, the compressor 
and outdoor fan will start up.   
T1-TS
On
Off
 
1.3.3.2 Outdoor Fan Running Guidelines 
For single-fan units: 
The outdoor fan will run following the compressor 
For double-fan units: 
The outdoor fans run depending on T4.