4-way cassette FCU    MCAC-KTSM-2012-02 
20                                                                                                          Capacity Tables 
 
 
 
1500 
∆t 
Air inlet temp. (20℃ DB) 
Water inlet temp. (℃) 
35 40  45  50  55  60  65  70 
TH  WF WPD  TH  WF WPD  TH WF WPD  TH WF WPD TH WF WPD TH WF WPD  TH  WF  WPD TH WF WPD
10  6.0   0.5   2.0   9.4   0.8   4.9   13.0  1.1   9.4   16.4  1.4  15.0  19.8  1.7  21.9  23.3  2.0  30.3   26.6  2.3   39.6  30.0  2.6  50.2 
8  6.6   0.7   3.8   10.3  1.1   9.3   13.8  1.5  16.7  17.2  1.9  25.9  20.6  2.2  36.9  23.9  2.6  49.9   27.3  2.9   64.9  30.6  3.3  81.8 
6  7.7   1.1   9.1   11.2  1.6  19.4  14.5  2.1  32.6  18.0  2.6  50.2  21.4  3.1  71.0  24.8  3.5  95.0   27.9  4.0  120.7  31.5  4.5  153.5 
Heating capacity modification coefficient table: 
Speed 
200 300 400 500 600 800 
TH TH TH TH TH TH 
High 1 1 1 1 1 1 
Mid 0.79 0.78 0.79 0.8 0.78 0.79 
Low 0.64 0.65 0.63 0.65 0.64 0.66 
Altitude modification coefficient table: 
Altitude TC  SC TH
500 0.98 0.95 0.95
1000 0.97  0.91  0.91
1500 0.95  0.86  0.86
2000 0.94  0.82  0.82
2500 0.93  0.78  0.78
3000 0.91  0.74  0.7