MCAC-UTSM-201606                             Midea 50Hz AC Fan Coil Unit Two-pipe Wall-mounted Series 
- 8 - 
Specifications 
Model 
MKG-500-B  MKG-600-B 
Power supply  V/Ph/Hz  220-240/1/50 
Air flow (H/M/L) 
m
3
/h  850/745/620  1020/915/780 
CFM  500/440/365  600/540/460 
Cooling 
Capacity (H/M/L)  kW  4.25/3.85/3.32  5/4.47/3.97 
Water flow rate  L/h  731    860   
Water pressure drop  kPa  31.8  42.5 
Heating 
Capacity (H/M/L)  kW  5.81/5.17/4.43  6.7/6/5.28 
Water pressure drop  kPa  30.2  39.7 
Power input  W  50  66 
Sound pressure level  dB(A)  39/33/28  40/34/29 
Fan motor 
Type  Low noise 4-speed fan motor 
Quantity  1 
Fan 
Type  Tangential fan 
Quantity  1 
Coil 
Row  2 
Diameter  mm  Φ7 
Tube pitch(a)  ×  row pitch(b) 
mm  21×13.37 
Dimension (W×H×D)  mm  785×315×26.74 
Fin spacing  mm  1.5 
Fin type  Hydrophilic aluminum 
Circuit  5 
Max. working pressure  MPa  1.6 
Body 
Net dimensions (W×H×D)  mm  1072×315×230 
Packing size (W×H×D)  mm  1180×415×315 
Net weight  kg  15.8  15.8 
Gross weight  kg  19.4  19.4 
Pipe 
connections 
Water inlet/outlet pipe  inch  G3/4 
Drain pipe  mm  ODΦ20 
Notes: 
1. H: high fan speed; M: medium fan speed; L: low fan speed 
2. Cooling Conditions: Entering Water 7°C, Temperature Rise 5°C, Entering Air Temperature 27°C DB,19°C WB. 
Heating Conditions: Entering Water 50°C, Enter air temperature 20°C, and water flow is same to the cooling conditions. 
3. Noise is tested in semi-anechoic test room.