AC Fan Coil Unit Two-pipe Wall-mounted Series
 
- 31 - 
12.7.4 E8: Fan motor malfunction 
    E8: Fan motor malfunction     
        No     
    Is the motor fan stuck 
Yes
Adjust the IDU fan 
        No     
   
Is the cable between the main board 
and the fan not connected or loose 
Yes Properly connect the cable
        No     
    Is the IDU input power abnormal 
Yes
Power failure: contact the 
power supply sector 
        No     
Between red and 
white:310V 
Between black and 
white:15V 
 
Is the voltage of the main board 
terminal CN24 abnormal 
No
Fan fault 
        No     
   
Replace the main board and check 
whether the problem is eliminated 
 
No 
        Yes     
    The device returns to normal     
 
 
12.7.5 EE:
 
Water-level switch malfunction   
EE: Water-level alarm malfunction     
    No 
   
Water-level switch connecting wire 
between switch and main board gets 
loose 
Yes 
Reconnect and ensure that the 
connection is reliable. 
  No 
 
 
There is something wrong with the water-
level switch 
Yes  Replace switch. 
  No   
 
Chip fault or chip foot sheds odd or chip is 
inverted.(correct mode is semicircular 
bent alignment) 
Yes 
Reinstall chip or install other chip 
with same model on the faulty unit to 
check whether there is something 
wrong with the chip. 
  No 
 
    No 
Main board error. For example, getting 
wet. 
Yes 
Replace main board.