Troubleshooting MCAC-UTSM-2008-05
62 Outdoor Units
5. E5 malfunction
LED indicates E5
Outdoor unit voltage protection
Check the voltage of outdoor unit power supply, whether the
voltage between L1 and N is about 198-254V
No
Replace the power board, then check whether the system can run normally
Check the power supply
Yes
Replace outdoor main board
Yes
Trouble is solved
No