MCAC-UTSM-2008-11  Capacity Tables 
Indoor Units  73 
MUB-36HRN1 (3 phase) 
Cooling 
Cooling  Outdoor conditions (DB) 
Indoor Conditions  (kW)  21ºC  28ºC  35ºC  43ºC 
21/15ºC DB/WB 
TC  10.82  10.29  9.77  9.35 
SC  8.00  7.92  7.81  7.85 
Input  3.11  3.38  3.53  3.64 
24/17ºC DB/WB 
TC  11.13  10.61  10.08  9.45 
SC  8.35  8.27  8.16  7.94 
Input  3.30  3.53  3.68  3.86 
27/19ºC DB/WB 
TC  11.34  10.82 
10.50 
9.77 
SC  8.39  8.33  8.19  8.01 
Input  3.38  3.56 
3.75 
3.94 
32/23ºC DB/WB 
TC  11.55  11.13  10.92  10.08 
SC  9.82  9.68  9.61  9.37 
Input  3.53  3.68  3.94  4.09 
 
Heating 
Heating  Outdoor conditions 
Indoor Conditions (DB)  (kW)  24/18ºC DB/WB  7/6ºC DB/WB  2/1ºC DB/WB  -5/-6ºC DB/WB 
15ºC 
TC  15.60  12.60  10.32  9.36 
Input  4.00  3.44  2.96  2.78 
20ºC 
TC  15.12  12.00  9.72  9.12 
Input  4.37  3.70  3.26  3.00 
27ºC 
TC  14.16  11.28  9.12  8.88 
Input  4.63  4.00  3.52  3.26 
Remark: 
TC : Total capacity ; kW 
SC: Sensible heat capacity ; kW 
Input: Input power ; kW