Page 25
T3 maintained above TCDE2 for 80 seconds.
Unit runs for 15 minutes consecutively in defrosting
mode.
If T4 is lower than or equal to -22°C and compressor
running time is more than TIMING_DEFROST_TIME,
if any one of the following conditions is satisfied,
defrosting ends and the machine switches to normal
heating mode:
Unit runs for 10 minutes consecutively in defrosting
mode.
T3 rises above 10°C.
The following two conditions apply only to certain models,
see tabel in section 3.1 for details.
Case 1:
If T3 is lower than 3°C and compressor running time
is more than 120 minutes, at this time, if T3 is lower
than TCDI1+4°C(39.2°F) for 3 minutes, the unit enters
defrosting mode.
If any one of the following conditions is satisfied,
defrosting ends and the machine switches to normal
heating mode:
T3 rises above TCDE1+4°C.
T3 maintained above TCDE2+4°C for 80 seconds.
Unit runs for 15 minutes consecutively in defrosting
mode.
Case 2:
If any one of the following conditions is satisfied, the
unit enters defrosting mode
If T3 or T4 is lower than -3°C(26.6°F) for 30
seconds,Ts-T1 is lower than 5°C and compressor
running time is more than 90min.
If T3 or T4 is lower than -3°C(26.6°F) for 30
seconds and compressor running time is more than
120min.
If any one of the following conditions is satisfied,
defrosting ends and the machine switches to normal
heating mode:
T3 rises above TCDE1+4°C.
T3 maintained above TCDE2+4°C for 80 seconds.
Unit runs for 15 minutes consecutively in defrosting
mode.
3.5.5 Evaporator Temperature Protection
When the evaporator temperature exceeds a preset
protection value, the compressor ceases operation.
3.6 Auto-mode
This mode can be selected with the remote controller
and the setting temperature can be changed between
17°C~30°C.
Case 1:
In auto mode, the machine selects cooling, heating, or
fan-only mode on the basis of T (T =T1-TS).
T Running mode
T>A Cooling
B≤∆TA Fan-only
T<B Heating*
Heating*: In auto mode, cooling only models run the fan
Indoor fan will run at auto fan speed.
The louver operates same as in relevant mode.
If the machine switches mode between heating and
cooling, the compressor will keep stopping for certain
time and then choose mode according to T.
Case 2:
In auto mode, the machine selects cooling, heating, or
fan-only mode on the basis of T1,Ts and T4.
If the setting temperature is modified, the machine
selects a new running function.
3.7 Drying mode
AC operates the same as auto fan in cooling mode.
When T1<17°C, the fan speed is lower than 30%, the
unit will operate at 30%.
Low Room Temperature Protection
If the room temperature is lower than 10°C, the
compressor ceases operations and does not resume
until room temperature exceeds 12°C.
All protections are active and the same as that in
cooling mode.
3.8 Sleep function
The sleep function is available in cooling, heating, or
auto mode.