Service manual 39
10.4.2.2 Outdoor fan running rules
The On-off outdoor units have single fan speed. The outdoor fan will run following the compressor
except when AC is in evaporator high temp. protection in heating mode ,condenser high temp.
protection in cooling mode, defrosting mode and the current protection.
10.4.2.3 Indoor fan running rules
In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low and
auto.
The auto fan:
10.4.2.4 Low evaporator coil temperature T2 protection
TE6
T2
On
Off
TE5
When the evaporator coil temp.T2 keeps lower than TE5 for 5 minutes, the compressor and outdoor
fan will shut off. When T2 is higher than TE6, the compressor and outdoor fan will restart up.
Model
TE5() TE6()
MS11M-09HRN1 / MO11M-09HN1
2 7
MS11M-12HRN1 / MO11M-12HN1
3 12
MS11M-18HRN1 / MO11M-18HN1
3 14
MS11M-24HRN1 / MO11M-24HN1