11.3 Diagnostic chart
After energizing, no indicator is lighted and the air conditioner can’t be operated.
For the 9K and 12K models:
Be sure all the wires(including power wires and connection wires)
is OK
Check if AC 115V (or 208-230V) power supply outputs to outdoor
PCB
Check if AC 115V (or 208-230V) exists at primary coil of
transformer
Check if AC 12V and AC 35V (+5%) exist at second coil of
transformer in the outdoor PCB
Outdoor PCB is defective
Yes
Yes
No
Take off the secondary plug of transformer, and then check if AC
12V and AC 35V (+5%) exist at secondary coil of transformer
No
Transformer is defective