Specifications
Page 37
INDOOR
AIRFLOW
(CMH)
OUTDOOR
DB()
ID WB
()
16.0 18.0 19.0 22.0
ID DB
()
23.0 25.0 27.0 30.0 23.0 25.0 27.0 30.0 23.0 25.0 27.0 30.0 23.0 25.0 27.0 30.0
902
27
TC 5.3 5.3 5.4 5.5 5.6 5.6 5.6 5.6 5.7 5.7 5.7 5.8 6.2 6.2 6.2 6.2
S/T 0.73 0.88 0.97 1.00 0.60 0.75 0.84 1.00 0.52 0.66 0.75 0.90 0.33 0.46 0.54 0.69
PI 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.44
30
TC 5.2 5.2 5.3 5.4 5.4 5.4 5.4 5.5 5.6 5.6 5.6 5.6 6.0 6.0 6.0 6.0
S/T 0.74 0.89 0.98 1.00 0.60 0.75 0.85 1.00 0.52 0.67 0.76 0.92 0.33 0.46 0.54 0.70
PI 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.53 1.53 1.53 1.53
32
TC 5.1 5.1 5.2 5.2 5.3 5.3 5.3 5.4 5.5 5.5 5.5 5.5 5.9 5.9 5.9 5.9
S/T 0.74 0.90 0.99 1.00 0.61 0.76 0.86 1.00 0.52 0.67 0.76 0.93 0.32 0.46 0.55 0.71
PI 1.57 1.57 1.57 1.57 1.58 1.58 1.58 1.58 1.58 1.58 1.58 1.58 1.59 1.59 1.59 1.59
35
TC 4.9 5.0 5.0 5.1 5.2 5.2 5.2 5.2 5.3 5.3 5.4 5.5 5.7 5.7 5.7 5.7
S/T 0.75 0.91 1.00 1.00 0.61 0.77 0.87 1.00 0.52 0.68 0.77 0.93 0.32 0.47 0.55 0.71
PI 1.66 1.66 1.66 1.66 1.66 1.66 1.66 1.66 1.67 1.67 1.67 1.67 1.68 1.68 1.68 1.68
43
TC 4.5 4.5 4.5 4.6 4.7 4.7 4.7 4.8 4.8 4.8 4.9 4.9 5.2 5.2 5.2 5.2
S/T 0.78 0.96 1.00 1.00 0.63 0.80 0.90 1.00 0.53 0.70 0.80 0.99 0.32 0.47 0.57 0.90
PI 1.94 1.94 1.94 1.94 1.94 1.94 1.94 1.94 1.95 1.95 1.95 1.95 1.96 1.96 1.96 1.96
46
TC 4.3 4.3 4.3 4.4 4.5 4.5 4.6 4.6 4.7 4.7 4.7 4.7 5.0 5.0 5.0 5.0
S/T 0.79 0.98 1.00 1.00 0.63 0.82 0.92 1.00 0.54 0.71 0.82 1.00 0.31 0.48 0.57 0.92
PI 2.04 2.04 2.04 2.04 2.04 2.04 2.04 2.04 2.05 2.05 2.05 2.05 2.07 2.07 2.07 2.07
52
TC 3.9 3.9 4.0 4.0 4.1 4.1 4.1 4.1 4.2 4.2 4.2 4.2 4.6 4.6 4.6 4.6
S/T 0.83 1.00 1.00 1.00 0.66 0.86 0.98 1.00 0.55 0.74 0.86 1.00 0.30 0.48 0.59 0.97
PI 2.30 2.30 2.30 2.30 2.31 2.31 2.31 2.31 2.31 2.31 2.31 2.31 2.33 2.33 2.33 2.33
TC:Total Cooling Capacity (kW)
S/T:Sensible Cooling Capacity Ratio
PI:Power Input(kW)
Note: The table shows the case where the operation frequency of a compressor is fixed.