EasyManua.ls Logo

Minebea Intec PR 5230 - Special Hints for Devicenet and Ethernet-IP; Fieldbus Register

Minebea Intec PR 5230
303 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12.2.5 Special hints for DeviceNet and EtherNet-IP
With these eldbus types, the sequence of the bytes (only applicable for words and
individual bytes) is inverted.
With long words, this problem does not arise due to compensation by the rmware.
Sequence of bytes 03, e.g. with device type and software version, see table below.
Standard sequence Sequence for DeviceNet and EtherNet-IP
Byte 0 TYPE MSB Byte 0 SUBVERSION
Byte 1 TYPE LSB Byte 1 MAIN VERSION
Byte 2 MAIN VERSION Byte 2 TYPE LSB
Byte 3 SUBVERSION Byte3 TYPE MSB
Consequently, the sequence on the PLC side must be changed when using the DeviceNet
and EtherNet–IP eld bus types.
12.2.6 Fieldbus register
12.2.6.1 Register 0: I/O status bits (read)
Dynamic status
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Byte 0 Input 3 Input 2 Input 1
Byte 1 Output 3 Output 2 Output 1
Byte 2 Limit 3 Limit 2 Limit 1
Byte 3
12.2.6.2 Register 1: Scale status (read)
Dynamic status
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Byte 0 DIM STND INZSR CZERO BELOW0 OVL >Max ADUERR
Byte 1 E9 E6 E1 E3 E7
Byte 2 PowerFail ActionAc-
tive
CmdError
Byte 3 TareActive CalActive TestActive
Note:
Byte 0 corresponds to byte 7 in the output area; for weight error, see also the table in
Chapter 16.1.
Bit Description
ADUERR Error of analog conversion/load cell circuit (OR function of the E1,
E3, E7 bits).
Transmitter in eld housing PR 5230 12 Fieldbus interface
Minebea Intec EN-264

Table of Contents

Related product manuals