Once the option is enabled, the key is displayed, and a Disable button replaces the
Enable button.
Configuring Power Supply Redundancy on a Kaleido-X16
Power supply redundancy is an option on the Kaleido-X16, which can ship with a single
PSU. In order to avoid having the system dashboard display unnecessary alarms, there is a
check box in XAdmin to indicate the presence of the second PSU. By default, this option is
selected (both PSUs are monitored). Removing the check mark will stop the monitoring of
alarms for PSU B (its status is set to disabled, and therefore will not appear on the
dashboard).
Location of Slot A and Slot B in the front of the Kaleido-X16 frame
To configure the PSU B Installed option in XAdmin
1 Open a Web browser window and type the IP address of the Kaleido-X16 frame in the
address bar.
The Kaleido-X home page appears.
Notes
• The Kaleido-IP currently supports extraction of CC/subtitling and XDS data
(1
license/program), and display rotation. It is not yet possible to enable or
verify these options in XAdmin’s Status and Options page, for this
multiviewer model. Contact Technical Support for activation and
configuration instructions (see
Contact Us, on page 453).
• One CC/XDS Option key is needed per input card, and the extraction of CC
608, CC 708, XDS and Subtitling WST metadata are all activated as a single
option.
• After enabling the 3D Support option in XAdmin, refresh the current layout
or load another one, for the change to be reflected on the monitor wall.
• For a complete list of the options that can be enabled and disabled via the
XAdmin Status and Options page, see
Hardware and Software Options, on
page 383.
Slot A Slot BPSU A removed