2 SPECIFICATIONS
2.1 Performance Specifications
2 SPECIFICATIONS
This chapter describes the specifications of CC-Link IE Field Network Basic.
2.1 Performance Specifications
The following table lists the performance specifications of CC-Link IE Field Network Basic.
*1 It is the maximum number of connectable modules for a slave station controlled by the master station. It varies depending on the number
of stations occupied by a slave station. Ensure that the total number of occupied stations does not exceed the maximum number of
connectable modules.
*2 When using the programmable controller CPU (except for the R00CPU, R01CPU, and R02CPU) with the firmware version "28" or
earlier, refer to the following.
Page 9 Performance specifications vary depending on the version of the CPU module
*3 When using the CPU module with serial number earlier than "19042" (first five digits), refer to the following.
Page 9 Performance specifications vary depending on the version of the CPU module
Item Specifications
MELSEC iQ-R MELSEC iQ-F MELSEC-Q MELSEC-L
Number of connectable modules per
network
Master station 1
Slave station
*1
64 (16 4 groups)
*2
664 (16 4 groups)
*3
16
*3
Number of stations occupied by a slave station 1 to 4
Maximum number of link points per
network
RX 4096
*2
384 4096
*3
1024
*3
RY 4096
*2
384 4096
*3
1024
*3
RWr 2048
*2
192 2048
*3
512
*3
RWw 2048
*2
192 2048
*3
512
*3
Maximum number
of link points per
station
Master station RX 4096
*2
384 4096
*3
1024
*3
RY 4096
*2
384 4096
*3
1024
*3
RWr 2048
*2
192 2048
*3
512
*3
RWw 2048
*2
192 2048
*3
512
*3
Slave station RX 64 (1 station occupied)
128 (2 station occupied)
192 (3 station occupied)
256 (4 station occupied)
RY 64 (1 station occupied)
128 (2 station occupied)
192 (3 station occupied)
256 (4 station occupied)
RWr 32 (1 station occupied)
64 (2 station occupied)
96 (3 station occupied)
128 (4 station occupied)
RWw 32 (1 station occupied)
64 (2 station occupied)
96 (3 station occupied)
128 (4 station occupied)
UDP port number used in the cyclic transmission 61450
UDP port number used in the automatic detection of connected
device
Master station: An unused port number is assigned automatically.
Slave station: 61451
Transmission
specifications
Data transmission speed 100Mbps
Number of cascade
connections
100BASE-TX For the number of the connectable stages when using a switching hub, check with the
manufacturer of the switching hub used.
Network topology Star topology
Connection cable Ethernet cable compliant with the 100BASE-TX standard ( Page 18 Ethernet cable)
Maximum station-to-station distance 100m (ANSI/TIA/EIA-568-B (Category 5e) compliant)
Overall cable distance Depends on the system configuration