Loading...
*
The inputs from X044 to X047 and the outputs from Y024 to Y027 are occupied by the FX2N-8ER-ES/UL, but they
can not used.
2.11.2 Special function module address
Since you can attach multiple special function modules to a single base unit each module needs
to have a unique identifier so that you can address it to transfer data to and from it. Each module
is automatically assigned a numerical ID in the range from 0 7 (you can connect a maximum of
8 special function modules). The numbers are assigned consecutively, in the order in which the
modules are connected to the PLC.
Special function module addresses are not assigned to the following products:
Input/output powered extension units (e. g. FX
2N-32ER-ES/UL or FX2N-48ET-ESS/UL)
Input/output extension blocks (e. g. FX
2N-16EX-ES/UL or FX2N-16EYR-ES/UL)
Communication adapter (e.g. FX
3U-CNV-BD)
Interface adapter (e. g. FX
3U-232-BD
Special adapter (e. g. FX
3U-232ADP)
Extension power supply unit FX
3U-1PSU-5V
I/O Assignment The Hardware
2-42 MITSUBISHI ELECTRIC
X000 to X017
Y000 to Y017
Base unit
FX
3U-32MR/ES
Input extension block
FX
2N-16EX-ES/UL
(16 inputs)
X020 to X037 X040 to X043*
Y020 to Y023*
Input/output
extension block
FX
2N-8ER-ES/UL
(4 inputs / 4 outputs)
X050 to X057
Input extension block
FX
2N-8EX-ES/UL
(8 inputs)
24-
24+
SLD
SLD
SLD
L-
L-
SLD
L-
L-
L+
L+
L+
L+
FX2N-4AD-TC
FX -4AD-PT
2N
24-
24+
FX2N-4DA
V+
V+
V+
I+
I+
V+
I+
I+
VI-
VI-
VI-
VI-
FX -4DA
2N
D / A
24-
V+
V+
V+
I+
I+
V+
I+
I+
24+
VI-
VI-
FG
FG
VI-
VI-
FG
Special function
module 0
Special function
module 1
Special function
module 2

Table of Contents