6 Before Starting Positioning Operation
6.1 Various Positioning Operation and Buffer Memory Setting
28
FX3U-1PG User's Manual
6.1 Various Positioning Operation and Buffer Memory Setting
Setting items of the buffer memory in each operation mode are as follows.
Setting of the positioning parameter selection (BFM#32) determines whether the positioning parameter is
used or the extension positioning parameter is used.
For details on the positioning operations and the buffer memory, refer to the following sections.
→ For details on the buffer memory, refer to the Chapter 7.
→ For details on the JOG operation and mechanical zero return operation, refer to the Chapter 8.
→ For details on the positioning operation, refer to the Chapter 9.
: Setting items necessary for operation
: Setting items necessary to change operation speed and target address during the operation
: Setting items necessary for variable speed operation with acceleration/deceleration
: Setting items necessary for interrupt input via PLC
-
: Setting not necessary
BFM No.
Setting items
Operation mode
Positioning
parameter
Extension
positioning
parameter
JOG operation
DOG type mechanical zero return operation
Data-set type mechanical zero return operation
1-speed positioning operation
Interrupt 1-speed positioning operation
2-speed positioning operation
External command positioning operation
Variable speed operation
Interrupt stop operation
Interrupt 2-speed positioning operation
#0 #34, #33 Pulse rate
Required for machine system and combined system of
units.
#2, #1 #36, #35 Feed rate
#3 #37 Operation parameter
#5, #4 #39, #38 Maximum speed -
#6 #41, #40 Bias speed -
#8, #7 #43, #42 JOG speed ---------
#10, #9 #45, #44 Zero return speed (high speed)- --------
#11 #47, #46 Zero return speed (creep) - --------
#12 #48
Number of zero-point signal for
zero return
- --------
#14, #13 #50, #49 Zero-point address - - - - - - - -
#15 - Acceleration/deceleration time -
- #51 Acceleration time -
-#52Deceleration time -
#16 Starting delay time - - -
#18, #17 Target address Ι - - - - -
#20, #19 Operation speed Ι - - -
#22, #21 Target address ΙΙ - - - - - - - - -
#24, #23 Operation speed ΙΙ - - - - - - -
#25 Operation command
#32 Positioning parameter selection
#54, #53 Target address change value - - - - -
#56, #55 Operation speed change value - -
#57 Operation command ΙΙ - - - - - -