With terminal cover open
1.2 External dimensions and weight
(
*
1) 2- 4.5-diam mounting holes: FX3U-16M, FX3U-32M
(except FX3U-32MR/UA1)
4- 4.5-diam mounting holes: FX3U-48M, FX3U-64M,
FX3U-80M, FX3U-128M,
FX3U-32MR/UA1
FX3U-16M and FX3U-32M (except FX3U-32MR/UA1) do
not have the (*)-marked mounting holes.
(
*
2) FX3U-32MR/UA1 is equivalent to FX3U-48M.
(
*
3) FX3U-64MR/UA1 is equivalent to FX3U-80M.
Installation
35-mm-wide DIN rail or Direct (screw) mounting (M4)
2. Installation (general specifications)
As for installation of the input/output extension units/blocks, special
adapters and expansion boards, refer to FX3U Series User's Manual
- Hardware Edition.
No. Name
[1] Protective terminal covers (FX3U-M/-A is excluded)
[2] Power supply, Input (X) terminals
[3]
Terminal block mounting screws
(FX3U-16M terminal block cannot be installed/removed)
[4] Terminal names
[5] Output (Y) terminals
Model name
W:
mm (inches)
W1:
mm (inches)
Direct mounting
hole pitches
MASS
(Weight)
:
kg (lbs)
FX3U-16M 130 (5.12”) 103 (4.06”) 0.6 (1.32lbs)
FX3U-32M
(
*
2)
150 (5.91”) 123 (4.85”) 0.65 (1.43lbs)
FX3U-48M 182 (7.17”) 155 (6.11”) 0.85 (1.87lbs)
FX3U-64M (
*
3)
220 (8.67”) 193 (7.6”) 1.00 (2.2lbs)
FX3U-80M 285 (11.23”) 258 (10.16”) 1.20 (2.64lbs)
FX3U-128M 350 (13.78”) 323 (12.72”) 1.80 (3.96lbs)
[2]
[5]
[3]
[3]
[1]
[4]
W
W1
22
(0.87")
Unit: mm (inches)
90 (3.55")
80 (3.15")
86 (3.39")
(
*
1
)
9 (0.36")
Mounting hole pitches
*
*
INSTALLATION
PRECAUTIONS
Use the product within the generic environment specifications
described in section 2.1 of this manual.
Never use the product in areas with excessive dust, oily smoke,
conductive dusts, corrosive gas (salt air, Cl2, H2S, SO2 or
NO2), flammable gas, vibration or impacts, or expose it to high
temperature, condensation, or rain and wind.
If the product is used in such conditions, electric shock, fire,
malfunctions, deterioration or damage may occur.
Do not touch the conductive parts of the product directly. Doing
so may cause device failure or malfunctions.
Install the product securely using a DIN rail or mounting screws.
Install the product on a flat surface.
If the mounting surface is rough, undue force will be applied to
the PC board, thereby causing nonconformities.
When drilling screw holes or wiring, make sure cutting or wire
debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or
malfunctions.
Be sure to remove the dust proof sheet from the PLC's
ventilation port when installation work is completed. Failure to
do so may cause fire, equipment failures or malfunctions.
Connect the extension cables, peripheral device cables, input/
output cables and battery connecting cable securely to their
designated connectors.
Loose connections may cause malfunctions.
Turn off the power to the PLC before attaching or detaching the
following devices.
Failure to do so may cause device failures or malfunctions.
- Peripheral devices, display modules, expansion boards and
special adapters
- Extension units/blocks and the FX Series terminal block
- Battery and memory cassette
Notes
When a dust proof sheet is supplied with an unit, keep the
sheet applied to the ventilation slits during installation and
wiring work.
To prevent temperature rise, do not install the PLC on a floor, a
ceiling or a vertical surface.
Install it horizontally on a wall as shown in section 2.2.
Keep a space of 50 mm (1.97”) or more between the unit main
body and another device or structure (part A). Install the unit as
far away as possible from high-voltage lines, high-voltage
devices and power equipment.
WIRING
PRECAUTIONS
Cut off all phases of the power supply externally before
installation or wiring work in order to avoid damage to the
product or electric shock.
2.1 Generic specifications
(
*
1) The criterion is shown in IEC61131-2.
(
*
2) Dielectric withstand voltage and insulation resistance are
shown in the following table.
For dielectric with stand voltage test and insulation resistance
test of each product, refer to the following manual.
Refer to FX3U Series User's Manual - Hardware Edition.
(
*
3) For common grounding, refer to section 3.3.
(
*
4) The PLC cannot be used at a pressure higher than the
atmospheric pressure to avoid damage.
Item Specification
Ambient
temperature
0 to 55 C (32 to 131 F) when operating and -25 to
75 C (-13 to 167 F) when stored
Ambient
humidity
5 to 95 %RH (no condensation) when operating
Vibration
resistance
(
*
1)
Fre-
quency
(Hz)
Accele-
ration
(m/s
2
)
Half
amplitude
(mm)
Sweep Count
for X, Y, Z: 10
times
(80 min in
each
direction)
When
installed
on DIN
rail
10 to 57 - 0.035
57 to
150
4.9 -
When
installed
directly
10 to 57 - 0.075
57 to
150
9.8 -
Shock
resistance
(
*
1)
147 m/s
2
Acceleration, Action time: 11 ms, 3 times by
half-sine pulse in each direction X, Y, and Z
Noise
resistance
By noise simulator at noise voltage of 1,000 Vp-p,
noise width of 1 s, rise time of 1 ns and period of 30
to 100 Hz
Dielectric
withstand
voltage (
*
2)
1.5 kV AC for one
minute
Between each terminals and
ground terminal
500 V AC for one
minute
Insulation
resistance
(
*
2)
5 M or more by
500 V DC megger
Grounding
Class D grounding (grounding resistance: 100 or
less) <Common grounding with a heavy electrical
system is not allowed.> (
*
3)
Working
atmosphere
Free from corrosive or flammable gas and excessive
conductive dusts
Working
altitude
<2000 m (
*
4)
Terminal
Dielectric
strength
Insulation
resistance
Main units, Input/output extension units/blocks
Between power supply terminal
(AC power) and ground
terminal
1.5 kV AC for
one minute
5 M or more by
500 V DC megger
Between power supply terminal
(DC power) and ground
terminal
500 V AC for
one minute
Between 24 V DC service
power supply connected to
input terminal (24 V DC) and
ground terminal
500 V AC for
one minute
Between input terminal (100 V
AC) and ground terminal
1.5 kV AC for
one minute
Between output terminal (relay)
and ground terminal
1.5 kV AC for
one minute
Between output terminal
(transistor) and ground terminal
500 V AC for
one minute
Between output terminal (triac)
and ground terminal
1.5 kV AC for
one minute
Expansion boards, Special adapters,
Special function units/blocks
Between terminal of expansion
board and ground terminal
Not allowed Not allowed
Between terminal of special
adapter and ground terminal
500 V AC for
1 min
5 M or more by
500 V DC megger
Special function unit/block Each manual

Related product manuals