FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
PLC User's Manual - Positioning Control Edition
Built-in Positioning Functions
2 Specifications
2.5 Output Specifications
B - 29
A
Common Items
B
Built-in
Positioning
Functions
Apx.
Example
Connection
2.5 Output Specifications
2.5.1 FX3S Series main unit (Transistor Output)
This section describes the transistor output specifications of the FX3S Series main unit. Note that the
simultaneous turning-on rate is restricted for the main unit. For details on this restriction, refer to the following
manual.
Refer to the FX
3S Hardware Edition.
For MELSERVO Series amplifiers, use a sink input/sink output type PLC.
Pulse output terminals Y000 and Y001 are high-speed response output terminals.
To use the positioning instruction, adjust the load current of the NPN open collector to 10 to 100 mA (5 to 24 V DC).
Item Transistor output specifications
External voltage All outputs 5 to 30 V DC
Maximum
load
Resistance load All outputs
The total load current of resistance loads per common
terminal should be the following value or less.
- 1 point output common:0.5 A
- 4 points output common:0.8 A
Inductive load All outputs
The total of inductive loads per common terminal
should be the following value or less.
- 1 point output common:12 W/24 V DC
- 4 points output common:19.2 W/24 V DC
Open-circuit leakage current All outputs 0.1 mA or less at 30 V DC
ON voltage All outputs 1.5 V or less
Response
time
OFFON
Y000, Y001 5 s or less at 10 mA or more (5 to 24 V DC)
Y002 to Y015 0.2 ms or less at 200 mA or more (at 24 V DC)
ONOFF
Y000, Y001 5 s or less at 10 mA or more (5 to 24 V DC)
Y002 to Y015 0.2 ms or less at 200 mA or more (at 24 V DC)
Circuit insulation All outputs Photocoupler insulation
Indication of output motion All outputs LED is lit when the photocoupler is driven.
Item Description
Operation voltage range 5 to 24 V DC
Operation current range 10 to 100 mA
Output frequency 100 kHz or less
Downloaded from ManualsNet.com search engine