2 SPECIFICATIONS
2.3 Performance Specifications
2.3 Performance Specifications
The following table lists the performance specifications.
Items Specifications
CC-Link IE Field
Network Basic
Station type Master station
Maximum number of connectable stations
*1
32
Number of stations occupied by a slave station 1 to 4
Maximum number of link points per network RX 2048
RY 2048
RWr 1024
RWw 1024
Maximum number of link points per
station
Master
station
RX 2048
RY 2048
RWr 1024
RWw 1024
Slave
station
*2
RX 64/128/192/256
RY 64/128/192/256
RWr 32/64/96/128
RWw 32/64/96/128
UDP port number used in the cyclic transmission 61450
UDP port number used in the automatic detection of connected
device
Master station: An unused port number is assigned automatically.
Slave station: 61451
Transmission
specifications
Data transmission speed 100 Mbps
Interface RJ45 connector
Maximum station-to-station distance 100 m
Overall cable distance Depends on the system configuration
Number of cascade
connections
100BASE-TX For the number of the connectable stages when using a switching hub,
check with the manufacturer of the switching hub used.
Network topology Star topology
Hub
*3
Hubs with 100BASE-TX ports
*4
can be used.
Connection cable
*5
100BASE-TX Ethernet cable of category 5 or higher (STP cable)
General-purpose
Ethernet
communication
Transmission
specifications
Data transfer speed 100/10 Mbps
Communication mode Full-duplex or half-duplex
*3
Transmission method Base band
Interface RJ45 connector
Maximum segment length (Maximum distance
between hub and node)
100 m
*6
Number of cascade
connections
100BASE-TX 2 levels maximum
*7
10BASE-T 4 levels maximum
*7
Protocol type Socket communication
Number of connections Total of 32 connections
(Up to 32 external devices can access one FX5-ENET module at the
same time.)
Hub
*3
Hubs with 100BASE-TX or 10BASE-T ports
*8
can be used.
Connection cable
*5
100BASE-TX Ethernet cable of category 5 or higher (STP cable)
10BASE-T Ethernet cable of category 3 or higher (STP/UTP cable)
Number of ports 2
*9
Number of occupied I/O points 8 points
Applicable CPU module • FX5U CPU module (Ver. 1.110 or later)
• FX5UC CPU module
*10
(Ver. 1.110 or later)
Applicable engineering tool GX Works3 (Ver. 1.050C or later)
Number of connectable units 1 module