APPX
Appendix 4 Buffer Memory
77
A
Data link status of each station
Data link status of each station (Un\G4104 to Un\G4105)
Stores the slave station data link status for each station No.
*1 This status includes the case where a slave station has not responded to the first request from the master station due to a power-off of
the slave station. (The slave station is not judged as a faulty station because the data link status is not determined.)
Only the bit of the start station number turns on.
The status is not stored for the reserved stations and the station numbers after the maximum station
number.
This buffer memory can be used to monitor errors in slave stations, connected cables, and a connected
hub.
Total number of connected stations
Total number of connected stations (Un\G4112)
The total number of connected stations set in GX Works3 is stored. (Page 32 Network Configuration Settings)
Reserved station specification status of each station
Reserved station specification status of each station (Un\G4113 to Un\G4114)
Stores the setting state of the reserved station set with GX Works3. (Page 32 Network Configuration Settings)
Only the bit of the start station number turns on.
The status is not stored for the reserved stations and the station numbers after the maximum station
number.
Link scan information (group number 1)
Link scan information (group number 1) (Un\G4117 to Un\G4119)
Link scan information of group number 1 is stored.
Address bit Station number Description
Un\G4104 b0 1 station On: Faulty station
Off: Normally operating station
b1 2 station
b15 16 station
Un\G4105 b0 to b15 17 to 32 station
Address bit Station number Description
Un\G4113 b0 1 station On: Reserved station
Off: Other than reserved station
b1 2 station
b2 3 station
b15 16 station
Un\G4114 b0 to b15 17 to 32 station
Address Name Description
Un\G4117 Maximum link scan time (Unit: ms) The maximum link scan time value during cyclic transmission is stored. (Unit: ms)
Un\G4118 Minimum link scan time (Unit: ms) The minimum link scan time value during cyclic transmission is stored. (Unit: ms)
Un\G4119 Current link scan time (Unit: ms) The current link scan time value during cyclic transmission is stored. (Unit: ms)