APPX
Appendix 4 Buffer Memory
79
A
*1 The value set with GX Works3 is stored. (Page 32 Network Configuration Settings)
*2 When the IP address has not been set in the parameter, 0 is stored.
*3 When the count exceeds 65535, counting is continued from 1 again.
If the slave station specified with 'Diagnostic request information' (Un\G4127)" is disconnected, the
information current just before the disconnection is stored.
Diagnostic information 2
Diagnostic information 2 (Un\G4144 to Un\G4159)
When Diagnostic information 2 is valid (1 is stored in b8 to b15 of 'Diagnostic information status flag' (Un\G4128)), the
manufacturer code, model code, device version, module information, error code, and detailed module information are stored.
When Diagnostic information 2 is invalid (0 is stored in b8 to b15 of 'Diagnostic information status flag' (Un\G4128)), 0 is
stored.
If the slave station specified with 'Diagnostic request information' (Un\G4127)" is disconnected, the
information current just before the disconnection is stored.
Un\G4139 Accumulated number of timeouts After the END instruction of the scan where the bit 0 of 'Diagnostic information
display request' (Un\G4162) is turned off and on is executed, the accumulated
number of timeouts that occurred in a slave station specified in 'Diagnostic request
information' (Un\G4127) is stored.
0: No timeouts
1 to 65535: Number of timeouts (accumulated number)
*3
Un\G4140 Accumulated number of disconnection detection After the END instruction of the scan where the bit 0 of 'Diagnostic information
display request' (Un\G4162) is turned off and on is executed, the accumulated
number of disconnections that detected in a slave station specified in 'Diagnostic
request information' (Un\G4127) is stored.
0: No disconnections
1 to 65535: Number of disconnection detection (accumulated number)
*3
Un\G4141 to
Un\G4143
System area
Address Name Description
Un\G4144 Manufacturer code Manufacturer code of a slave station specified is stored.
Un\G4145 System area
Un\G4146 Model code Model code (lower) of a slave station specified is stored.
Un\G4147 Model code (upper) of a slave station specified is stored.
Un\G4148 Device version Device version of a slave station specified is stored.
Un\G4149 System area
Un\G4150 Own station module information Module information of a slave station specified is stored.
Un\G4151 Error code Latest error code of a slave station specified is stored.
Un\G4152 Detailed module information Detailed module information (lower) of a slave station specified is stored.
Un\G4153 Detailed module information (upper) of a slave station specified is stored.
Un\G4154 to
Un\G4159
System area
Address Name Description