M800VS/M80V Series Connection and Setup Manual
5 Installation
5.2 Noise Countermeasures
188
IB-1501613-A
5.2.2 Shield Clamping of Cables
The shield of the shield cable connected to the control unit and drive unit must be connected to the grounding plate to stabilize
operation while preventing malfunctioning due to noise.
The shield can be connected to the grounding plate with lead wires or clamp fittings. Refer to the following drawings to treat
the shield cable.
Example of connection with lead wire
Example of connection with clamp fitting
Peel part of the cable sheath and expose the shield as shown in the drawing. Press the exposed part against the grounding
plate with the cable clamp fittings.
If the cables are thin, several can be bundled and clamped together.
Use adequate force when tightening the cable so that the wire material is not damaged.
Connect each grounding plate together and ground them at one point.
Cable
Unit
Lead wire
Example of lead wire treatment
Cable
Shield
Soldering
Cable
Grounding plate
Shield
Grounding plate
Cable
Clamp fitting
Shield
Unit
Clamp fitting
Less than
0.8m