M800VS/M80V Series Connection and Setup Manual
40 Appendix 5: EMC Installation Guidelines
40.5 Measures for Wiring in Panel
601
IB-1501613-A
40.5 Measures for Wiring in Panel
Cables act as antennas to propagate unnecessary noise, and thus must be appropriately shielded and treated.
The following measures must be sufficiently considered for the cables (J210/J303) that carry out high-speed communication.
40.5.1 Precautions for Wiring in Panel
If the cables are led unnecessary in the panel, they will pick up noise. Pay attention to the device layout and wire length so
that the wiring length is as short as possible.
Always connect the grounding wire to the FG terminal indicated on the device.
Keep the distance between the drive line and encoder cable to the drive section motor as far apart as possible when wiring.
Do not lead the power supply wire around the panel without using a filter.
Noise
Device Device Device DeviceDevice Device
NF
Partition
plate
Device
Radiated
noise
AC input
Conductive
noise
Flow
out
Noise
filter