9 - 2
LOADING AND INSTALLATION9.
9.1.2 Precautions on base unit installation
(1) Installation dimensions
Mounting dimensions of each base unit are as follows:
Unit: mm
*1 The tolerance of Ws and Hs is 0.3 mm.
(2) Module installation position
*2 In the case the height of the wiring duct is 50mm or less. In other cases, the figure should be
40mm or more.
*3 The figure should be 20mm or more if an extension cable is connected without removing the
next module.
*4 The figure should be 80mm or more for the connector type module.
QA1S33B QA1S35B QA1S38B QA1S65B QA1S68B
W 255 325 430 315 420
Ws *1 235 305 410 295 400
H 130
Hs *1 110
I/O0
I/O7
I/O6
I/O5
I/O4
I/O3I/O2
I/O1
W
Ws
POWER
5V
SG
CPU
Hs
H
FG
OUT
5mm or more
*3
5mm or more
30mm or
more
*2
30mm or
more
The shadowed area represents
the ceiling, wiring duct, or parts
in the control panel.
20mm or
more
*4
Programmable
controller
Door
Control
panel