Appendix 2. Selection
A2 - 7
Appendix 2-2-2 Calculating the positioning frequency
Select the regenerative resistor so that the positioning frequency DP (times/minute) calculated from the
regenerative resistor capacity P
R (W) and regenerative energy ER (J) consumed by the regenerative
resistor is within the range shown in expression (2-10). For the unbalance axis, calculate using the
regenerative energy E
R per reciprocation operation, and judge the number of operation cycles for rising
and lowering as DP.
PR
DP < 48
E
R
(times/minute) (2-10)
Table 2-5 List of regenerative option correspondence
Regenerative
resistor type
(Japan
Resistor)
GZG80
W26
OHMJ
GZG200
W26
OHMJ
GZG300
W20
OHMJ
GZG400
W13
OHMJ
GZG400
W8
OHMJ
GZG200
W120
OHMJ
3 units
c
onnected
in parallel
GZG200
W39
OHMJ
3 units
c
onnected
in parallel
GZG300
W39
OHMJ
3 units
c
onnected
in parallel
GZG200
W20
OHMJ
3 units
c
onnected
in parallel
GZG300
W20
OHMJ
3 units
c
onnected
in parallel
GRZG400
-2
OHMJ
4 units
c
onnected
in serial
Regenerative
resistor unit
type
MR-RB32 MR-RB30 MR-RB50 MR-RB31 MR-RB51 MR-RB65
Regenerative
capacity
40W 100W 150W 200W 200W 300W 300W 500W 300W 500W 800W
Resistance
value
26Ω
26 20 13 8 40 13 13 6.7 6.7 8
MDS-R-V1-20
{ { {
MDS-R-V1-40
{ { { { { {
MDS-R-V1-60
{ { { { {
MDS-R-V1-80
{ { { { {
MDS-R-V2-2020
{ { {
MDS-R-V2-4040
{ { { {
MDS-R-V2-6040
{ { { {
MDS-R-V2-6060
{ { { {
MDS-R-V2-8040
{ { { {
MDS-R-V2-8060
{
{ { {
MDS-R-V2-8080
{
{ { {
(Note) Types indicated with a cannot be used when driving the HF353 motor.