6. LOADING AND INSTALLATION
MELSEC-A
POINTI
.(1)
Ground
the
surge
absorber
(El)
an
the
PC (E2) separately from each
other.
(2) Select a
surge
absorber
making allowance
for
power
voltage
rises.
(2) Wiring of I/O
equipment
(a)
Applicable
size of wire
to
the
terminal
block
connector
is 0.3 (18)
to
2 mm
2
(14 AWG). However, it is
recommended
to
use
wires
of 0.75
mm
2
(18 AWG)
for
convenience.
(b) Separate
the
input
and
output
lines.
(c) I/O signal wires
must
be at least 100 mm (3.94 in) away from
high-voltage
and
large-current main
circuit
wires.
(d) When
the
I/O signal wires
cannot
be
separated
from
the
main circuit
wires
and
power
wires,
ground
on
the
PC side
with
batch-shielded
cables.
Under
some
conditions
it may be preferable
to
ground
on
the
other
side.
PC
Shielded cable
~-----7'
~
I
Input
<>-----.
Output
9--0--1
DC
(e) If wiring has been
done
with piping,
ground
the
piping.
(f) Separate
the
24 VDC I/O cables from
the
100 VAC
and
200
VAC
cables.
(g) If wiring over 200 m (656.2 tt) or
longer
distance,
trouble
can be
caused by leakage
currents
due
to
line
capacity
referring
to
the
I/O
error
examples in
the
A2C I/O
module
User's Manual.