4. A2CCPU
--------------------
MELSEC-A
(4) Self-diagnosis
The PC CPU
conducts
self-checks when it is powered up or reset. For
further
details, see Section 4.3.1.
4.1.3
END processing
END processing returns the A2C to step 0 after
the
END (FEND) instruction
execution to allow repeated operation processing.
(1) CPU error check
Checks battery power, etc.. See Section 4.3.1 for details.
(2) Timer/counter processing
Updates timer/counter present values and
contact
status. For further
details, see Section 4.1.4 and 4.1.5.
(3) Sampling trace processing
Stores
the
specified device status to
the
sampling
trace
area when
the
sampling trace is executed every scan (after END execution)
(4) Operation state check
Checks operation state of the A2C and switches to
the
RUN, STOP or
PAUSE state. For transition processing to
the
RUN, STOP and PAUSE
states, see Section 4.1.9.
(5) Constant scan processing
Allows
the
repeated
operation
processing
to be
initiated
after
the
specified constant scan time (set to special
data
register D9020) is
reached.
(6) Link refresh processing
After receiving a link refresh request signal from
the
MELSECNET
data
link, link refresh processing is executed.
The A2CCPUP21/R21 can set link refresh enable/disable by M9053 and
DI/EI instructions.