4.A2CCPU
--------------------
MELSEC-A
I
4.4.1
Memory capacity setting
(1) The A2C provides 32K byte user memory area.
The following data can be stored in
this
user memory area.
(a) Parameters
(b)
Main programs
Sequence programs
Microcomputer programs
(c) File registers
(d) Comments
(e) Status latch
•
(I) Sampling trace
Allocation of user memory area sets
the
areas where each data should
be stored.
•
Parameter area
4K
bytes
TIC
setting value area
Main program area
2 to
16K
bytes
(1
to
BK steps)
Sampling trace
area
Status latch I Data area
IUser memory area I
area
IFile register
26
- [main program
area
32K
bytes
File register area
(K
bytes)]
K
bytes
Comment
area
Fig. 4.24
User
Memory
Area
Allocation
(2) The first 20K bytes in the user memory area is write protected.
If the memory protect switch will be set
ON
for
operation, file register
area and status latch area must not be within the write-protect area (first
20K bytes).
I
Memory
protected
j
20K
bytes
12K
bytes
Fig. 4.25
Memory
Protect
Areas
4-53