REPLACEMENT OF THE MELSECNET/10 (REMOTE I/O NETWORK)
5 - 28
5
(5) Parameter of parallel remote sub-master station
: Compatible, : Partial change required, × : Incompatible
(6) Parameter of remote I/O station
When mounting the intelligent function module on the remote I/O station, set the parameter.
When mounting only I/O modules, the operation is available even if the parameter is not set. (It is
operated with default value.)
: Compatible, : Partial change required, × : Incompatible
Parameter
name
Description
Compat-
ibility
Precautions for replacementQnA/QnAS series
MELSECNET/10 module
Q series
MELSECNET/H module
Network
parameter
Network type
-
Cannot be configured on the
remote I/O network of
MELSECNET/H.
Configure two networks.
Starting I/O No.
Network No.
Refresh parameters
Routing parameters
Valid module during other
station access
Parameter
name
Description
Compat-
ibility
Precautions for replacementA/AnS/QnA/QnAS series
MELSECNET/10 module
Q series
MELSECNET/H module
PLC
parameters
- PLC system setting
New parameter of MELSECNET/H
(The number of empty slots, etc. is
set.)
- PLC RAS setting
New parameter of MELSECNET/H
(The operation mode and error
check at an error are set.)
- Operation setting
New parameter of MELSECNET/H
(The parameters for transmitting
between devices are set.)
- I/O assignment setting
New parameter of MELSECNET/H
(The I/O assignment of remote I/O
station, etc. is set.)
Network
parameter
-
Ethernet
New parameter of MELSECNET/H
(The network parameter of
Ethernet module mounted on the
remote I/O station is set.)
CC-Link
New parameter of MELSECNET/H
(The network parameter of CC-
Link module mounted on the
remote I/O station is set.)
Remote
password
- Remote password setting
New parameter of MELSECNET/H
(The remote password of Ethernet
module and serial communication
module, etc. mounted on the
remote I/O station is set.)