REPLACEMENT OF CC-LINK
6 - 15
6
(b) Output signal
: Compatible, : Partial change required, × : Incompatible
Output signal
Signal name
Compat-
ibility
Precautions for replacement
AJ61QBT11/A1SJ61QBT11 QJ61BT11N
Yn0 Refresh specification Prohibited to use
Refreshed automatically. Delete the sequence
program of the section corresponding to the
function.
Yn1
Prohibited to use Prohibited to use
Yn2
Yn3
Yn4 Module reset request Prohibited to use ×
Delete the sequence program of the section
corresponding to the function.
When the switch setting is changed, turn the power
supply of programmable controller system OFF
ON or reset the programmable controller CPU.
Yn5 Prohibited to use Prohibited to use
Yn6
Data link startup request from
buffer memory parameters
Prohibited to use
Delete the sequence program of the section
corresponding to the function, and set parameters
with GX Works2/GX Developer or with dedicated
instruction (RLPASET instruction).
Yn7 Prohibited to use Prohibited to use
Yn8
Data link startup request from
E
2
PROM parameters
Prohibited to use
Delete the sequence program of the section
corresponding to the function, and set parameters
with GX Works2/GX Developer or with dedicated
instruction (RLPASET instruction).
Yn9 Prohibited to use Prohibited to use
YnA
Parameter registration request to
E
2
PROM
Prohibited to use
Delete the sequence program of the section
corresponding to the function, and set parameters
with GX Works2/GX Developer or with dedicated
instruction (RLPASET instruction).
YnB
Prohibited to use Prohibited to use
YnC
YnD
E
2
PROM erasure request
Prohibited to use
Delete the sequence program of the section
corresponding to the function, and set parameters
with GX Works2/GX Developer or with dedicated
instruction (RLPASET instruction).
YnE
Prohibited to use Prohibited to use
YnF
Y(n+1)0
Y(n+1)1
Y(n+1)2
Y(n+1)3
Y(n+1)4
Y(n+1)5
Y(n+1)6
Y(n+1)7
Y(n+1)8
Y(n+1)9
Y(n+1)A
Y(n+1)B
Y(n+1)C
Y(n+1)D
Y(n+1)E
Y(n+1)F