EasyManua.ls Logo

Mitsubishi Electric Melsec-F FX2NC Series - Page 74

Mitsubishi Electric Melsec-F FX2NC Series
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FX2NC Series Programmable Controllers Power supply 4.
4-4
Figure 4.2 : EX.wiring
DC/DC
EX.FX
2NC
-16M
24V DC5V DC
EX.FX
2NC
-16EX
EX.FX
2NC
-16EX
o
MC
PL
MC
MC MC
n
p
q
r
s
t
s
u
v
w
w
11
EX.FX
2NC
-16EYT
*1
*1
*1 It is recommended to use the same power
source to power the main unit, input extension
blocks and special function blocks. If two sources
are required, follow the below guidelines:
- Supply power to the input extension blocks and
special function blocks before or at the same
time the main unit is powered.
- The power supplies may be cut the same time
after ensuring system safety.
n
Power supply 24V DC +20% -15%
Ripple voltage (p-p) 5% or less
o
Circuit protector or Fuse
p
Emergency stop
q
Power supply switch
r
Power ON pilot indicator
s
Power supply for loads
t
Grounding resistor 100
or less (class D)
u
Fuse
v
Main unit
w
Input extension blocks
Output extension block
11

Table of Contents