7 Applied Instructions
7.5 Data Operation
237
FXCPU Structured Programming Manual
(Basic & Applied Instruction)
1
Outline
2
Instruction List
3
Configuration of
Instruction
4
How to Read
Explanation of
Instructions
5
Basic Instruction
6
Step Ladder
Instructions
7
Applied
Instructions
8
Interrupt Function
and Pulse Catch
Function
A
Relationships
between devices
and addresses
Related instructions
1. RST
As an independent reset instruction for devices, RST instruction can be used for bit devices (Y, M and S) and
word devices (T, C, D and R).
2. FMOV
FMOV instruction is provided to write a constant (example: K0) at one time. By using this instruction, "0" can
be written to word devices (KnY, KnM, KnS, T, C, D and R) at one time.
Cautions
1) The FX0, FX0S or FX0N PLC does not support the instructions of pulse operation type.
To execute pulse operation, make the instruction execution condition pulse type.
2) Specify same type of devices in the devices specified by and . The device number of the device
specified by should be smaller than or equal to the device number of the device specified by .
If the device number of the device specified by is larger than the device number of the device
specified by , only one device specified by is reset.
3) When specifying the high-speed counter, ZRST instruction is handled as the 16-bit type, but 32-bit
counters can be specified in and .
However, it is not possible to specify a 16-bit counter in the device specified by and specify a 32-bit
counter in the device specified by ; and should be a same type.
Program example
4) Some restrictions to applicable devices
S1:The FX
3U, FX3UC and FX3G PLCs only are applicable.
S2:The FX3U and FX3UC PLCs only are applicable.
RST
EN ENO
d
M0
X001
RST
EN ENO
d
TN0
RST
EN ENO
d
D0
K0 is written to D0 to D99 at one time.
X002
K0 D0
FMOV
EN
s
n
ENO
d
K100
16-bit counter
Command input
CN230
ZRST
EN ENO
d1
d2
CN180
32-bit counter
Command input
CN199
ZRST
EN ENO
d1
d2
CN180
CN230
ZRST
EN ENO
d1
d2
CN200