EasyManua.ls Logo

Mitsubishi Electric MELSEC FX Series - Page 322

Mitsubishi Electric MELSEC FX Series
838 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Applied Instructions
7.6 High Speed Processing
320
FXCPU Structured Programming Manual
(Basic & Applied Instruction)
2. Total number of output pulses
Set the total number of output pulses specified by as follows.
•For FX
3U and FX3UC PLCs : 16-bit instruction1 to 32,767PLS
32-bit instruction1 to 2,147,483,647PLS
•For FX
3G PLC : 16-bit instruction110 to 32,767PLS
32-bit instruction110 to 2,147,483,647PLS
•For FX
2N and FX2NC PLCs : 16-bit instruction110 to 32,767PLS
32-bit instruction110 to 2,147,483,647PLS
When setting a value less than "110", the operation is as follows.
PLC version V3.00 or before : The pulses are not generated normally.
PLC version V3.00 or later : One tenth of the maximum frequency is generated.
If the maximum frequency is 100 Hz or less, "10 Hz" is generated.
•For FX
1S, FX1N and FX1NC PLCs : 16-bit instruction110 to 32,767(PLS)
32-bit instruction110 to 999,999(PLS)
When setting a value less than "110", the pulses are not generated normally.
3. Acceleration/deceleration time
Set the acceleration/deceleration time specified by as follows.
For FX
3U, FX3UC and FX3G PLCs: 50 to 5000 (ms)
For FX2N and FX2NC PLCs: 5000 (ms) or less
Follow, however, the conditions a) through d).
a) Make the acceleration/deceleration time be 10 times or more the PLC's maximum scan time (value of
D8012 or greater). If set to less than 10 times, the acceleration/deceleration timing becomes instable.
b) The following equation defines the allowable minimum that can be set as the acceleration/
deceleration time.
If setting a value less than the equation indicates, the error in the acceleration time becomes large. If
set to less than "90000/ , operation takes place while rounding it up to "90000/ ".
c) The following equation defines the allowable maximum that can be set as the acceleration/
deceleration time.
d) The number of speed changes (steps) for the acceleration/deceleration is fixed to "10 times" as shown
in the previous page.
If unable to set the PLC to these conditions, lower the maximum frequency specified by .
•For FX1S, FX1N and FX1NC PLCs: 50 to 5000(ms)
4. Pulse output
Only a transistor output on the main unit or Y000 or Y001 on a special high speed output adapter
*1
can be
specified in .
*1. Special high speed output adapters can be connected only to the FX
3U PLC.
When using the PLSR instruction with a relay output type FX
3U PLC, a special high speed output
adapter is required.
The duration of the ON/OFF pulses is 50% (ON = 50%, OFF = 50%)
The pulse output is controlled by the dedicated hardware not affected by the sequence program (operation
cycle).
If the command input is set to OFF during continuous pulse output, the output from the device specified by
turns OFF.
5. Specifying input and output variables
When handling 32-bit data in a structured program, a 16-bit device cannot be specified directly as in the case
of a simple project. Use a label to handle 32-bit data.
A 32-bit counter can be specified directly as it is a 32-bit long device.
Use a global label to specify a device.
90000
s1
s3
5
×
×
s1
s3
818
s2

Table of Contents

Other manuals for Mitsubishi Electric MELSEC FX Series

Related product manuals