7 Applied Instructions
7.28 FX3U-CF-ADP
797
FXCPU Structured Programming Manual
(Basic & Applied Instruction)
1
Outline
2
Instruction List
3
Configuration of
Instruction
4
How to Read
Explanation of
Instructions
5
Basic Instruction
6
Step Ladder
Instructions
7
Applied
Instructions
8
Interrupt Function
and Pulse Catch
Function
A
Relationships
between devices
and addresses
Detailed explanation of setting data
Details of the setting data in the FLWR instruction are as shown below.
Cautions
1) The FLWR instruction is completed abnormally if a CompactFlash
TM
card is not mounted.
2) The user should pay close attention to the number of times data is written when the writing destination is
set to the CompactFlash
TM
card because data is written every time the FLWR instruction is executed.
For example, if data is written to the CompactFlash
TM
card every one minute, data is written 100,000
times in approximately 2 months.
3) Even if the writing destination is set to the buffer inside the CF-ADP, data is written to the
CompactFlash
TM
card in the case of overwriting.
4) The FLWR instruction writes data to the CompactFlash
TM
card after the internal buffer inside the CF-ADP
becomes full when the writing destination is set to the buffer. Data stored in the internal buffer inside the
CF-ADP is erased when a (instantaneous or long) power interruption occurs.
5) When the data type is a data name (K8), the user can specify only the head line position before writing
other data. Index and DATE TIME are added automatically.
6) The FLWR instruction may require several scans to acquire data. Take proper measures such as saving
acquired data in another device if data consistency is required.
7) It is necessary to set the device number in multiples of 16 when a bit device is specified in and the
data type is set to anything other than bit type. When a word device is specified in and the data type
is set to bit, the FLWR instruction acquires data to be written from the least significant bit of the specified
device.
8) When is "K7" or "K8", 00H, which indicates the end of the string, must be added to the end of the
character string.
9) The FX
3U and FX3UC PLCs supports the instruction at V2.61 or later.
The FX
3UC-32MT-LT-2 PLC is due to be upgraded later.
Setting items Description Data Type
File ID
K0 to K63
ANY16
Head of devices which store data to be written.
Specify the head of devices which store the data to be written to the CompactFlash
TM
card.
ANY_SIMPLE
Data write parameter
Specify the data writing type
K0 : Mixed type
K1 : Bit type
K2 : Decimal type (16-bit)
K3 : Decimal type (32-bit)
K4 : Hexadecimal type (16-bit)
K5 : Hexadecimal type (32-bit)
K6 : Real numbers(Floating point data) Exponent expression type (32-bit)
K7 : Character string (512 half-width/full-width characters maximum)
K8 : Data name :Character string consisting of up to 32 half-width/full-width
characters. Index, DATE TIME are added automatically.
ANY16(0..4)
+1
Specify the line position of the writing destination, or specify additional writing.
Line position of the writing destination : K1 to specified maximum number of lines
Additional writing : K-1
+2
Specify the data column position in the writing destination.
Column position : K1 to K254
Additional writing : K-1
+3
Number of written data points
K1 to K254
+4
Writing destination
K0 : CompactFlash
TM
card
K1 : Buffer inside the CF-ADP
Line position after writing
K1 to specified maximum number of lines
ANY16(0..1)
+1
Column position after writing
K1 to K254
Channel number used by the CF-ADP
K1 : ch1
K2 : ch2
ANY16