EasyManua.ls Logo

Mitsubishi Electric MELSEC FX Series - Page 123

Mitsubishi Electric MELSEC FX Series
162 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FX communication
FX
2N
-232IF 10
10-3
10
Note : “W : For write” can be used for read also. Undefined BFM Nos. are not allowed to be used
in the program.
*1 : Spare buffers used in the interlink connection mode.
BFM
No.
Name Setting range
Initial
value
R:For read
W:For write
#20
Time from CS ON to send start 0 to 32,327 (X 10 ms) 0 W
#21
Time from completion of actual
send to RS OFF
(completion flag ON)
0 to 32,327 (X 10 ms) 0 W
#28
Status
0R
#29
Error code
0R
#30
Model code
K7030 R
#1000
Send byte count
0 to 512 (when data length is 16 bits)
0 to 256 (when data length is 8 bits)
0W
#1001
to
#1256
Send buffers
0W
#2000
Receive byte count
0 to 512 + 30 *1
0 to 256 + 15 *1
0R
#2000
to
#2256
Receive buffers
0R
#2257
to
#2271
Spare receive buffers for interlink
connection mode
0R