EasyManua.ls Logo

Mitsubishi Electric MELSEC FX Series - Page 140

Mitsubishi Electric MELSEC FX Series
162 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FX communication
FX
2N
-232IF 10
10-20
b ) Command <BFM #1>
M0
b0:Send/receive enable (ER ON)
M1
b1:Send command
M2
b2:Receive completion reset command
M3
b3:Error reset
c ) Receive upper limit byte count <BFM #2>
8bytes
d ) Header and terminator <BFMs #4 to #11>
BFMs #4 and #8 (send/receive header): 02H (STX)
BFMs #6 and #10 (send/receive terminator):03H (ETX)
e ) Status <BFM #28>
b0
M10:Send completion b8
M18:RS(RTS)
b1
M11:Receive completion b9
M19:ER(DTR)
b2
M12:Receive time-out b10
M20:Undefined
b3
M13:Error occurrence b11
M21:Undefined
b4
M14:Receive suspended b12
M22:DR(DSR)
b5
M15:Undefined b13
M23:CD(DCD)
b6
M16:Being sent b14
M24:CS(CTS)
b7
M17:Being received b15
M25:CI(RI)
f ) Send byte count <BFM #1000>
9 bytes
g ) Send buffers <BFMs #1001
>
9-byte send data “123456789” is prepared in ASCII code in accordance with the send byte
count specified above.
h ) Receive buffers <BFMs #2001
>
8-byte receive data specified in accordance with the receive upper limit byte count (BFM
#2) is read to the data registers D301 to D304 in the programmable controller.
10th byte is not sent.
2 (32 H) 1 (31 H )
4 (34 H) 3 (33 H )
6 (36 H) 5 (35 H )
8 (38 H) 7 (37 H )
* * 9 (39 H)
2nd byte
4th byte
6th byte
8th byte
10th byte
1st byte
3rd byte
5th byte
7th byte
9th byte
Upper byte Lower byte
(BFM#1001)
(BFM#1002)
(BFM#1003)
(BFM#1004)
(BFM#1005)

Table of Contents