E-7
2 Specifications
A
Common Items
B
FX
3U
-4AD
FX
3UC
-4AD
C
FX
3U
-4AD-ADP
D
FX
3G
-2AD-BD
E
FX
3U
-4DA
F
FX
3U
-4DA-ADP
G
FX
3G
-1DA-BD
H
FX
3U
-3A-ADP
I
FX
3U
-4AD-PT
-ADP
J
FX
3U
-4AD-PTW
-ADP
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
FX3U-4DA (4-channel Analog Output)
2.2 Power Supply Specifications
2.2 Power Supply Specifications
2.3 Performance Specifications
*1. Adjustment of the offset or gain value will not affect the resolution. In output mode 1 or 4, however, the
offset/gain cannot be adjusted.
*2. The offset and the gain should satisfy the following condition:
1 V (Gain - Offset) 10 V
*3. The offset and the gain should satisfy the following condition:
3 mA (Gain - Offset) 30 mA
*4. When the external load is less than 30 k
Ω
, please use the output corrective function by load resistance.
For a detailed description of the output corrective function by load resistance,
refer to Subsection 5.4.17.
Item Specifications
D/A conversion
circuit drive power
24 V DC ±10 %, 160 mA
(It is necessary to supply 24 V DC from the terminal block.)
CPU drive power
5 V DC, 120 mA
(Since the internal power is supplied from the main unit, it is not necessary to supply power
externally.)
Item
Specifications
Voltage output Current output
Analog output
range
-10 V to +10 V DC
(External load: 1 kΩ to 1 MΩ)
0 mA to 20 mA DC, 4 mA to 20 mA DC
(External load: 500 Ω or less)
Offset
*1
-10 V to +9 V
*2
0 mA to 17 mA
*3
Gain
*1
-9 V to +10 V
*2
3 mA to 30 mA
*3
Digital input With sign, 16bits, binary 15bits, binary
Resolution 0.32 mV (20 V / 64,000) 0.63 μA (20 mA / 32,000)
Overall accuracy
*4
Ambient temperature: 25 °C±5 °C
±0.3 % (±60 mV) for 20 V full scale
Ambient temperature: 0 °C to 55 °C
±0.5 % (±100 mV) for 20 V full scale
Ambient temperature: 25 °C±5 °C
±0.3 % (±60 μA) for 20 mA full scale
Ambient temperature: 0 °C to 55 °C
±0.5 % (±100 μA) for 20 mA full scale
Time required for
D/A conversion
1 ms (The number of selected channels will not affect this value.)
Insulation method
The photocoupler is used to insulate the analog output area from the PLC.
The DC/DC converter is used to insulate the analog output area from the power supply unit.
Channels are not insulated from each other.
Number of I/O
points occupied
8 points (Taken from either the input or output points of the PLC.)