G-15
4 Programming
4.1 Writing of D/A Conversion Data
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
FX3G-1DA-BD (1-channel Analog Output)
A
Common Items
B
FX
3U
-4AD
FX
3UC
-4AD
C
FX
3U
-4AD-ADP
D
FX
3G
-2AD-BD
E
FX
3U
-4DA
F
FX
3U
-4DA-ADP
G
FX
3G
-1DA-BD
H
FX
3U
-3A-ADP
I
FX
3U
-4AD-PT
-ADP
J
FX
3U
-4AD-PTW
-ADP
4. Programming
This chapter describes how to create programs that can output the analog data using the 1DA-BD.
4.1 Writing of D/A Conversion Data
1) The input digital data will be converted into analog data and then output to the terminals.
2) If data is stored in the special devices, the averaging time can be set, and the output mode can be
specified.
3) In the FX
3G Series PLC (40-point or 60-point type), special auxiliary relays (10 points) and special data
registers (10 points) are assigned to each analog expansion board, board A and B connected to option
connector 1 and 2 respectively, in that order.
In the FX
3G Series PLC (14-point or 24-point type) and FX3S Series PLC, special auxiliary relays (10
points) and special data registers (10 points) are assigned.
→ For a detailed description of special device assignment, refer to Section 4.2.
•FX
3S Series PLC
•FX
3G Series PLC
The analog expansion board connected to option connector 1 is regarded as the "board A", and the analog
expansion board connected to option connector 2 is regarded as the "board B".
*1. Board B is not available in the FX
3G Series PLC (14-point and 24-point type).
FX3S Series PLC
Sequence Program
Special auxiliary relays:
M8260 to M8269
Special data register:
D8260 to D8269
D/A
FX
3G-1DA-BD
Option connector
FX3G Series PLC
Sequence Program
Special auxiliary relays:
M8260 to M8269
Special data register:
D8260 to D8269
Board A
FX
3G-1DA-BD
D/A D/A
FX3G-1DA-BD
Board B
*1
Option connector 1 Option connector 2
Special auxiliary relays:
M8270 to M8279
Special data register:
D8270 to D8279