116
APPX
Appendix 1 Operations of when the MC/MCR instructions are used to control EN
Retentive timer (low-speed timer/timer/high-speed timer), counter, and long counter
The following describes operations of the retentive timer (low-speed timer/timer/high-speed timer), counter, and long counter.
Ex.
A subroutine-type FB using a low-speed retentive timer
When "Yes" is selected for "Use MC/MCR to Control EN"
The current count value remain unchanged. ((1) in the following figure). The coil turns off ((2) in the following figure).
When "No" is selected for "Use MC/MCR to Control EN"
The current count value and the current state of the coil remain unchanged. ((1) in the following figure).
Sc: Scan
ST0 (Count): T0 (count value)
ST0 (Coil): T0 (coil)
EN is turned off. (User operation)
The coil turns off, but the current count value and the current state of the contact remain unchanged. (CPU module operation)
Sc: Scan
ST0 (Count): T0 (count value)
ST0 (Coil): T0 (coil)
EN is turned off. (User operation)
The values remain unchanged. (CPU module operation)
SM400
ENO
EN
OUT ST0 K3
END
ST0 (Count)
EN
ST0 (Coil)
(1)
(2)
Sc
012 3333
ST0 (Count)
EN
ST0 (Coil)
(1)
Sc
012 3333
(1)